Input power – Rockwell Automation 1336VT 5-300 AMP (2.2-160KW) User Manual
Page 30
Specifications
Chapter 4
4-3
Input Power
Voltage:
380-460V AC
±
10%.
Frequency:
48 to 62Hz.
Phase:
3-phase.
AC Input Overvoltage Trip:
570V AC.
AC Input Undervoltage Trip: 275V AC.
Bus Overvoltage Trip:
810V DC
Bus Undervoltage Trip:
388V DC
Line Transient Protection:
Line transients up to 5,000 volts peak, 320
Joules.
Logic Power Ride-Thru:
2 seconds or longer –– subject to the
integrity of user supplied external circuits.
Control Logic Noise:
Showering arc transients from 350 to 2,000
Immunity
volts peak.
Table 4.3 Ċ 1336VT Input Current and kVA
Input Power
Factor
Rating
kVA In
kVA In
kVA In
Displacement
Amps In
Code
380V AC
415V AC
460V AC
Angle
kW/kVA
5.6
003
3.7
4.0
4.5
0.95
0.85
7.5
005
4.9
5.4
6.0
0.95
0.85
11.4
007
7.5
8.2
9.1
0.95
0.85
14.6
010
9.6
10.5
11.6
0.95
0.85
22.0
015
14.5
15.8
17.5
0.95
0.85
28.0
020
18.4
20.1
22.3
0.95
0.90
35.0
025
23.0
25.2
27.9
0.95
0.90
44.0
030
29.0
31.6
35.1
0.95
0.90
54.0
040
35.5
38.8
43.0
0.95
0.90
67.0
050
44.1
48.2
53.4
0.95
0.90
78.0
060
51.3
56.1
62.1
0.95
0.90
97.0
075
63.8
69.7
77.3
0.95
0.90
124.0
100
81.6
89.1
98.8
0.95
0.90
154.0
125
101.4
110.7
122.7
0.95
0.90
178.0
150
117.2
127.9
141.8
0.95
0.90
235.0
200
154.7
168.9
187.2
0.95
0.90
296.0
250
194.8
212.8
235.8
0.95
0.90