Terminal Block TB2

The drive is capable of operating from an optional Local or Remote

Control and Signal Wiring

Control Panel with minimum connections to terminal block TB2. When
required, external operator elements may be connected to provide
additional drive control. Additional drive control functions and status
outputs are also available for use at TB2 as detailed on the following pages.

Pot

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

Wiper

Pot

High

Pot

Low

External

Speed Pot

+

+

+

+

CR1

CR2

CR3

CR3

CR4

CR4

ISOL

Analog

Meter

0–10V

Pulse

Source

4–20mA

At

Fault

(Not)

Drive

(Not)

Run

Speed

Fault

Alarm

Drive

Alarm

Shield

To

Pulse
Input

Fro

m

D/A

To

A/D

2

To

A/D

3

To

A/D

1

+5V

DC

1.4k

215

215

100

100

47.5k

200

49.9Ω

53.3k

75k

100

3.42k

Chassis
Ground

Signal

Common

Maximum

Recommended

Signal

Wire Group ❶

Wire Size ❷

Torque ❸

Terminals 1, 2, 3

External Speed Potentiometer

5

14 AWG

7 In-Lbs

Terminals 3 and 4

Signal Common

5

14 AWG

7 In-Lbs

Terminals 5, Signal Common

0-10V DC

5

14 AWG

7 In-Lbs

Terminals 6, Signal Common

4-20mA

5

14 AWG

7 In-Lbs

Terminals 7 and 8

Pulse Train

6

14 AWG

7 In-Lbs

Terminals 9, Signal Common

Meter Output

5

14 AWG

7 In-Lbs

Terminals 10 and 11

At Speed Contact

3

14 AWG

7 In-Lbs

Terminals 11 and 12

Run Contact

3

14 AWG

7 In-Lbs

Terminals 13, 14, 15

Fault Contacts

3

14 AWG

7 In-Lbs

Terminals 16, 17, 18

Drive Alarm Contacts

3

14 AWG

7 In-Lbs

❶ Wire group number chart, page 6-3.

❷ 2.50 mm

2

.

❸ .79 N-m.