Specifications

Chapter 4

4-4

Output Power

Waveform:

Sine coded pulse width modulated waveform.

Voltage:

0 to applied input voltage, 380V AC, 415V AC, or 460V
AC (maximum output voltage cannot exceed applied input
voltage).

Frequency Range:

0 to 250Hz with programmable minimum and maximum
limits.

Frequency

Digital —

Resolution:

Preset speeds (serial interface or pulse train input) to
0.005Hz of set frequency within the minimum and
maximum limits.

Analog —
Equal divisions between minimum and maximum limits to
the nearest 0.005Hz as a function of signal type.

Local speed pot (MOD-FA2 only), 1003 divisions.

Remote speed pot (TB2, Terminals 1, 2 and 3), 633
divisions.

0 to 10V DC input (TB2, Terminals 4 and 5), 976
divisions.

4 to 20mA input (TB2, Terminals 4 and 6), 726 divisions.

Frequency

Digital Frequency Source: 0.0013% of set frequency,

Regulation:

0 to 40

°

C ambient temperature range.

Volts-per-Hertz:

Fully programmable.
– Minimum 1 to 14.3V/Hz through local programming.
– Wider ranges available through optional programming.