Drive and option identification – Rockwell Automation 1336VT 5-300 AMP (2.2-160KW) User Manual
Page 15
2
Chapter
2-1
Drive and Option Identification
The following is an explanation of the catalog numbering system for
1336VT Adjustable Frequency AC Drives and options. The catalog
number is coded to identify the drive power rating and can be found on the
drive shipping carton.
1336VT
B 015
EAE
FA2
L2
S1
Bulletin
Drive
Enclosure
Options
Options
Options
Number
Rating
Type
1336VT Drive Catalog Numbers
Bulletin Number
The Allen-Bradley reference number identifying the type or family of
products.
Drive Ratings
A group of four characters coded to indicate input voltage and output
power rating.
The first character indicates the input voltage range of the drive.
Drives with a code “B” are suitable for operating from any one of the
following voltage inputs: 380/415/460V AC, 50/60 Hz, 3-phase.
Fan Transformer Reconnection for Alternate Drive Input Voltages
Important:
For drives rated 5-52 Amp, reconnection of Fan Transformer T1 is not
necessary.
For drives rated 65-300 Amp, Fan Transformer T1 must be reconnected for
380 or 415V operation. If Fan Transformer T1 is not connected to match
the incoming voltage, overtemperature fault F08 may occur. Refer to
Chapter 6 for wiring details.