Specifications

Chapter 4

4-7

Required Control Inputs (cont.)

Speed Reference

Speed reference sets the drive operating frequency. A speed reference input
may come from:

A Control Panel speed potentiometer.

A user supplied 10k

remote speed potentiometer connected to terminal

block TB2. Refer to Chapter 6 — Wiring.

A 4-20mA analog signal connected to terminal block TB2. Refer to
Chapter 6 — Wiring.

A 0-10V DC analog signal connected to terminal block TB2. Refer to
Chapter 6 — Wiring.

A pulse train input signal connected to terminal block TB2. Refer to
Chapter 6 — Wiring.

One of seven preset speed signals connected to the optional L1, L2, or
L3 Logic Interface Board, or the optional G2 Remote I/O Interface
Board. Refer to Appendix A — Logic Interface Options and the
1336-MOD-L1, L2 or L3 instruction manual or the 1336-MOD-G2
instruction manual.

Auxiliary

A maintained True input or a maintained closed contact will permit the
drive to start, run, or jog. A momentary False input or an open contact will
disable drive output and generate Fault F02. An auxiliary input may come
from:

A user supplied maintained contact or switch connected to the optional
L1, L2 or L3 Logic Interface Board. Refer to Appendix A — Logic
Interface Options and the 1336-MOD-L1, L2, or L3 instruction manual.

The Main Control Board when Jumper J9 is installed between Pins 9 and
10. Refer to Chapter 6 — Wiring, page 6-16.