Specifications

Chapter 4

4-9

Load Requirements

A balanced 3-phase inductive motor load is typical. Other motor loads may
require application assistance.

Contact Outputs

The following contact outputs are available as standard:

Run:

1 N.O. contact, closed when drive is running.

At Speed:

1 N.O. contact, closed when the drive is at command speed
(within 0.5% of maximum programmed speed), or the
drive reaches the set point reference frequency
programmed by Parameter 77.

Fault:

1 set of Form C contacts that change state on drive fault or
loss of power.

Drive Alarm:

1 set of Form C contacts that change state to indicate that
the drive is operating outside of rated limits and that a fault
is imminent.

Drive Alarm Conditions are:

Drive output current is above 115% of rated current.

Drive output current is above the MOPC limit set by

Parameter 36.

Bus voltage is above 110% of nominal input voltage. A

continued rise in bus voltage may result in Parameter 11
Decel Frequency Hold affecting the decel ramp, or fault
F05 Bus Overvoltage.

Bus voltage is below 85% of nominal input voltage.

Precharge not complete.

Parameter 14 Auto Restart is active.

Analog Outputs

0-5V DC output programmable to represent output frequency or percent of
drive load current.

Drive Displays

Programming

Display frequency and drive control source. May be

and Display

toggled to program and display 60 drive parameters

Panels:

–– 5-14, 16-50 and 72-86. Should a fault occur while the
drive is running, the panel will display the fault code.

Bus Charged:

Internal neon display to indicate bus voltage is greater than
40V DC.