Publication 1746-UM010B-EN-P - April 2001

Installing and Wiring 2-9

7. At the source-end of cables from mV devices (See Figure 2.3

and Figure 2.4):

remove the drain wire and foil shield

apply shrink wrap as an option

connect to mV devices keeping the leads short

Figure 2.4 Cable Preparation to Minimize Electrical Noise Interference

Wires

3/8”

Make
unshielded
wires as
short as
possible.

Limit braid length to 12” or
less. Solder braid to lug on
bottom row of I/O chassis
bolts.

Connect I/O

chassis bolt to

earth ground

Solder drain wires to
braid at casing.

Make unshielded wires
as short as possible.

3/8”

Signal
Wires

Terminal
Block

Chnl 0

Chnl 1

Chnl 2

Chnl 3

n/c

Cables

IMPORTANT

If noise persists, try grounding the opposite end of
the cable. Ground one end only.