Rockwell Automation 1746-BTM Barrel Temperature Control Module User Manual User Manual

Page 39

Advertising
background image

Publication 1746-UM010B-EN-P - April 2001

Configuring the Module 3-13

Table 3.B Block Header (word 0 / N10:0) = 8801 (-30719 decimal)

Loops 1-4

Word #

Set a bit or enter a value

1

2

3

4

bit

to Configure

Bit Select or Range

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

1

26

51

76

0-1

operation mode

Monitor, No PID Control

0

0

Control loop with PID

0

1

Disable loop

1

0

2-5

input type

Type J

0

0

0

0

Type K

0

0

0

1

6

alarm enable

Disable = 0; Enable = 1

X

7-8

TC break configuration

disable PID loop (CV=0)

0

0

Use thermal runaway
CV

0

1

Use manual mode CV

1

0

9

reserved

10-11

Autotune gains

low gains

0

0

medium gains

0

1

high gains

1

0

very high gains

1

1

12

Barrel control

Barrel=0;Non-barrel=1

X

13

Zone

Inner=0; Outer=1

X

14-15

reserved

2

27

52

77

0-15

High CV limit %

-100.00 thru +100.00%

default = +100.00%

3

28

53

78

0-15

Low CV limit %

-100.00 thru +100.00%

default = 0.00%

4

29

54

79

0-15

CV for TC break

-100.00 thru +100.00%

default = 0.0

5

30

55

80

0-15

Standby setpoint

0.0 thru 3276.7°

default = 0.0

6

31

56

81

0-15

Heat on time (min.)

0.00 thru 100.00 sec.

default = 0.00

7

32

57

82

0-15

Heat TPO period

0.00 thru 100.00 sec.

default = 5.00

8

33

58

83

0-15

Cool on time (min.)

0.00 thru 100.00 sec.

default = 0.00

9

34

59

84

0-15

Cool TPO period

0.00 thru 100.00 sec.

default = 5.00

10

35

60

85

0-15

PV alarm rate

-3276.8 thru 3276.7°/s

default = 0.0

11

36

61

86

0-15

Low temp alarm

-3276.8 thru 3276.7°/s

default = +999.9

12

37

62

87

0-15

High temp alarm

-3276.8 thru 3276.7°/s

default = +999.9

13

38

63

88

0-15

Low deviation

-3276.8 thru 3276.7°/s

default = +999.9

14

39

64

89

0-15

High deviation

-3276.8 thru 3276.7°/s

default = +999.9

15

40

65

90

0-15

Alarm dead band

0.0 thru 10.0°

default = 0.0

16

41

66

91

0-15

Thermal Integrity Loss

0 thru 100°

default = 5

17

42

67

92

0-15

Integrity Rate

0 thru 100 minutes

default = 20

18

43

68

93

0-15

ramping

0 thru 100°/min.

default = 0

19

44

69

94

reserved

20

45

70

95

0-15

Non-barrel autotune
disturb size

0.00-100.00%

default = 10.00

21

46

71

96

0-15

Startup
aggressiveness factor

0 thru 100

default = 0 for heat or cool, only; 25 for heat/cool

<=25 <=50

<=75 <=99

reserved