Publication 1746-UM010B-EN-P - April 2001

5-2 Control and Autotune a Loop

Figure 5.1 Control Mode Selections and Loop Operation

Autotune a Loop

The BTM module uses the output image table to control loop
operation. See Table 5.C on page 5-8 for the listing of words and
bits. Operating Commands to Loops 1-4

Use the following as a guide:

Requirements for Autotune

Start autotune from a steady–state temperature. For best results,
do a cold start. If the temperature fluctuates, autotune may not
provide accurate results.

The runtime setpoint for autotune must be at least 50

o

F (28.7

o

C) above current temperature or autotune will not start.

through the output image table

Control Mode Selections
Disable the Loop

Monitor the Loop

Control the Loop

Loop Operation
Hold CV=0, and no temperature or alarms

Hold CV=0, but monitor temperature and provide
temperature and alarms in the status block

Disable Loop Control

Enable Loop Control

Manual Mode

Automatic Mode

The manual output value in the configuration block
is used as the CV value

through the M1 configuration block

The PID algorithm generates the CV value