Publication 1746-UM010B-EN-P - April 2001

Control and Autotune a Loop 5-5

1. Assume using data table N10 in the following example. Set initial

conditions:

Set to zero Output image buffer table words 188–191 for
loops 1–4.

In the sample code, it zeros manual outputs to remove
control signals from loops.

2. Download the M1 Configuration File by setting N7:12/00 = 1.

3. Download the M0 Autotune File by setting N7:12/01 = 1.

4. Verify that the M1 Configuration File downloaded:

a. Check input image buffer words 164–167 bits 03, 04 for loops

1–4 to verify:

bit 03 = 1 module received a valid M1 file for the loop

bit 04 = 0 no parameter errors for the loop.

If bit 04 (parameter error) is set for any loop, look for the
error code in N10:212–215.
Refer to Locating Error Code Information on page 8-2.

b. Check input image buffer words 168–171 bits 00–02 for loops

1–4 to verify that the module:

bit 00 = 1 enabled PID control

bit 01 = 0 put loop into manual mode

bit 02 = 1 used runtime setpoint

Table 5.A Configuration File N10 Data Table Example

N10:1 bits 00

01 set for PID control

N10:26 bits 00

01 set for PID control

N10:51 bits 00

01 set for PID control

N10:76 bits 00

01 set for PID control

remaining bits/words set for your application

Table 5.B Data Table Example:

Output image buffer table words 180–183

bits 00–03 for loops 1–4.

bit 00

1 enables PID control

bit 01

0 puts loop into manual mode

bit 02

1 uses runtime setpoint

bit 03

1 enables autotune