This chapter provides troubleshooting guidelines.

Troubleshooting with LED
Indicators

The front panel of the module contains five green LED indicators for
channel status and one green LED indicator for module status.

We present a table of indications, probable causes, and recommended
action. See Table 8.A on page 8-3 and Table 8.B on page 8-4 for a
listing of error codes.

INPUT

ISOLATED

CHANNEL
STATUS

MODULE STATUS

0

2

1

3

LED: When: Indicates

Channel
Status

On channel is correctly configured
when you enable the channel
Flashing channel fault condition

Module
Status

Flashing communication occurring between
SLC processor and BTM module

On self-check completed OK

Indication

Probable Cause

Recommended Action:

all indicators
are OFF

no power to module

check power to I/O chassis
recycle power as necessary

module performing self–check

wait until self check is complete

module performing calibration

wait until calibration is complete

possible short on the module
LED failure

replace module

channel status
indicator is ON

channel is correctly configured
when you enable the channel

normal operation

during calibration, the channel is
properly configured for the high–end of
millivolt range

normal calibration

channel status
indicator is flashing

fault condition, such as open circuit or
an under/over range condition

correct fault condition

during calibration, the channel is
properly configured for the low–end of
millivolt range

normal calibration