Specifications, Specifications -10 – Rockwell Automation 1746-BTM Barrel Temperature Control Module User Manual User Manual

Page 26

Advertising
background image

Publication 1746-UM010B-EN-P - April 2001

2-10 Installing and Wiring

Specifications

Backplane Current
consumption

110 mA at 5V dc
85 mA at 24V dc

Backplane power consumption 0.6W maximum (0.55W @ 5V dc, 2W @ 24V dc)

Number of channels

4 (backplane and channel-to-channel isolated)

I/O chassis location

any I/O module slot except 0

A/D conversion method

sigma-delta modulation

Input filtering

analog filter with low pass digital filter

Normal mode rejection
between [+]input and [-]input

greater than 50 dB at 50 Hz
greater than 60 dB at 60 Hz

Common mode rejection
between inputs and chassis
ground

greater than 120 dB at 50/60 Hz with 1K ohm
imbalance

Channel bandwidth (-3db)

8 Hz

Calibration

once every six months

Isolation

1000V transient or 150 VAC continuous
channel-to-channel or channel-to-backplane

Agency
Certifications
When product or
packaging is
marked:

Listed Industrial Control Equipment

N223

Certified Process Control Equipment
Certified for use in Class I, Division 2, Groups A, B, C, D or
nonhazardous locations

Marked for all applicable acts

Marked for all applicable directives

Advertising