Using the pid equation, Using the pid equation -4 – Rockwell Automation 1746-BTM Barrel Temperature Control Module User Manual User Manual

Page 44

Advertising
background image

Publication 1746-UM010B-EN-P - April 2001

4-4 Setting Autotune and Gains Values

If the loop is slow in reaching the set point either at start–up or at a
change of set point, (See Figure 4.2) you may be able to improve the
loop response by doing one or more of the following (in order of
effectiveness):

1. increase the proportional gain

2. increase the integral gain

3. decrease the derivative gain

Figure 4.2 Loop Slow to Set Point

Using the PID Equation

The module provides dependant PID control action. Dependent
control action can be represented by the equation

The module is capable of performing PID control by calculating the
solution to an approximation of the PID equation. The approximation
is represented by the equation:

Set Point

CV

K

p

E

K

i

E D

t

K

z

E

d

t

d

------

+

0

t

+

=

Where:
CV = Control variable
K

p

= Proportional gain (no units)

E = Error (SP-PV or PV-SP)
K

i

= Integral gain (repeats/seconds)

K

z

= Derivative gain (seconds)

t = Time

CV

K

p

E

K

i

E

t

K

z

E

t

-------

+

0

t

+

=

E

0

t

t

E

1

t

E

2

t

E

3

t

etc

+

+

+

=

Where:

.....

Advertising