Control and Autotune a Loop 5-3

Set the TPO period smaller than the system dead time. Autotune
algorithm may calculate excessive gains if system dead time is
less than the TPO period. This may cause the PV to overshoot

Figure 5.2 Set TPO Period

The autotune algorithm does not take the temperature to
setpoint. When autotune is complete, the zones will return to
the mode (auto or manual) that was selected before autotune.

Figure 5.3 Autotune setpoint zones

Temperature

Output (CV)

system dead time

1 TPO period

System dead time should be larger than one
TPO period for autotune to work properly

Time

t

0

output (CV)
changed

Temperature

system dead

time

maximum slope

Return to the control mode
that was selected before
autotune

autotune
complete