Publication 1746-UM010B-EN-P - April 2001

Troubleshooting the Module 8-3

Table 8.A Configuration Error Codes

Code

Description

0

No error

1

Run setpoint is invalid

2

Manual control value is < -100% or > +100%

10

Heat system gain is less than 0

11

Heat time constant is less than 0

12

Heat dead time is less than 0

13

Cool system gain is less than 0

14

Cool time constant is less than 0

15

Cool dead time is less than 0

20

Heat proportional gain is less than 0

21

Heat integral gain is less than 0

22

Heat derivative gain is less than 0

23

Cool proportional gain is less than 0

24

Cool integral gain is less than 0

25

Cool derivative gain is less than 0

30

Loop operational mode is invalid

31

Thermocouple type is invalid

32

Maximum CV allowable is < -100%, > +100%, or max CV < min. CV

33

Minimum CV allowable is < -100% or > +100%

34

Control value when TC break detected is< -100 or > +100%

35

Standby setpoint is invalid

36

Heat minimum TPO cycle time is < 0 or > 100

37

Heat maximum TPO cycle time is < 0, > 100, or min. TPO > max TPO

38

Cool minimum TPO cycle time is < 0 or > 100

39

Cool maximum TPO cycle time is < 0, > 100, or min. TPO > max TPO

40

PV rate alarm degrees per second is invalid

41

Low temperature alarm is invalid

42

High temperature alarm is invalid

43

Low deviation alarm is invalid

44

High deviation alarm is invalid

45

Temperature alarm deadband is < 0 or > 10

46

Thermal Integrity Loss value is < 0- or > 100

47

Integrity Rate in minutes < 0 or > 100

48

Setpoint ramp rate is < 0

49

reserved

50

Nonbarrel autotune disturbance size is < 0% or greater than 100%

51

Startup aggressiveness factor is <0 or > 100