Publication 1746-UM010B-EN-P - April 2001

4-6 Setting Autotune and Gains Values

PID Gains/Autotune Block, M0 File for Loops 1–4

Note: Refer to Download and Upload Settings on page 9-3 for
download command bits.

IMPORTANT

Word numbers for loops 1–4 are in left–most
columns. For corresponding NX:xx address, add 110
to word the number.

Table 4.B PID Gains/Autotune
(N10:110-158): Block Header (word 0 / N10:110) = 880B (-30709 decimal)

Loops 1-4

Autotune Values (N10:111-134)

1

2

3

4

To Configure

Range

1

7

13 19 Heat gain

0.00 thru 327.67°/sec.

2

8

14 20 Heat time constant

0.0 thru 3276.7 sec.

3

9

15 21 Heat dead time

0.0 thru 3276.7 sec.

4

10 16 22 Cool gain

0.00 thru 327.67°/sec.

5

11 17 23 Cool time constant

0.0 thru 3276.7sec

6

12 18 24 Cool dead time

0.0 thru 3276.7 sec.

Loops 1-4

PID Gains Values (N10:135-158)

1

2

3

4

To Configure

Range

25 31 37 43 Heat proportional

0.000 thru 32.767

26 32 38 44 Heat integral

0.0000 thru 3.2767 rpts/
sec.

27 33 39 45 Heat derivative

0.0 thru 3276.7 sec.

28 34 40 46 Cool proportional

0.000 thru 32.767

29 35 41 47 Cool integral

0.0000 thru 3.2767 rpts/
sec.

30 36 42 48 Cool derivative

0.0 thru 3276.7 sec.