Installing the dh-485 communication cable, A-10, Incorrect – Rockwell Automation 1747-L40 SLC 500 Fixed Hardware Style User Manual

Page 115

Advertising
background image

Appendix A
Setting Up the DH-485 Network

A–10

Installing the DH-485 Communication Cable

The communication cable consists of a number of cable segments
daisy–chained together. The total length of the cable segments cannot
exceed 1219 m (4000 ft).

When cutting cable segments, make them long enough to route them from
one link coupler to the next with sufficient slack to prevent strain on the
connector. Allow enough extra cable to prevent chafing and kinking in the
cable.

Link Coupler

1747-AIC

Link Coupler

1747-AIC

Link Coupler

1747-AIC

Connector

Connector

Connector

Belden

#9842

Belden

#9842

Belden

#9842

DH-485

Interface

Peripheral

CPU

Power

DH-485

Interface

Peripheral

CPU

DH-485

Interface

Peripheral

CPU

Power

Power

Important: We only recommend a network that is daisy–chained. For

example, we do not recommend the following:

Connector

Connector

Connector

Belden

#9842

Belden

#9842

Belden

#9842

Incorrect

Advertising