Example heat dissipation calculation, Example worksheet for calculating heat dissipation, This worksheet shows you how to calculate the – Rockwell Automation 1747-L40 SLC 500 Fixed Hardware Style User Manual

Page 141

Advertising
background image

Control System

Appendix D
Calculating Heat Dissipation for the SLC 500

D–4

If your controller consisted of the following hardware components, you
would calculate heat dissipation as shown in the example worksheet below.

Hardware

Components

Catalog Number

Minimum Watts

Maximum Watts

Fixed Controller

1747-L20A

10.5

15.0

Input Module

1746-IA16

0.425

4.8

Output Module

1746-OA16

1.85

9.3

Peripheral Device

1747-DTAM

2.5

2.5

Example Worksheet for Calculating Heat Dissipation

Procedure

Heat Dissipation

1.

Calculate the heat dissipation for your fixed controller.

Write in the watts (calculated watts or maximum watts, see page D-1)

dissipated by the controller, I/O and specialty modules, and peripheral

device attached to the controller. Add these values together.

Catalog Number Heat Dissipation

Fixed Controller

_________

_________

Expansion Chassis

Slot 1 (if applicable

) _________

_________

Slot 2 (if applicable)

_________

_________

Peripheral Device

_________

_________

Total:

_________

Place Total on this Line --->

_______

W

2.

Convert to BTUs/hr. Multiply the total heat dissipation of your SLC

500 fixed control system by 3.414.

x 3.414

Total heat dissipation of the SLC 500 control system:

_______

BTUs/hr

Example Heat Dissipation

Calculation

Advertising