Chapter 8
Troubleshooting

8–5

The Following

Error Exists

Probable Cause

Recommended Action

System

Inoperable, No

Major CPU

F lt D t t d

User Program

Logic Error

Monitor logic in Run mode and verify desired I/O status.
Refer to either the Hand-Held Terminal User Manual ,

Catalog Number 1747-NP002, or the Advanced

Programming Software User Manual, Catalog Number

1747-NM002.

j

Faults Detected

Defective I/O

Devices or I/O

Wiring

Test inputs and outputs according to I/O troubleshooting

procedures starting on page

8-8

.

The Following

Error Exists

Probable Cause

Recommended Action

CPU Memory

Error

Cycle power.

CPU Fault

Faulty Memory

Module

1. Remove power and then remove the memory module

from the controller.

2. Re-energize the controller.
If steady CPU FAULT LED changes to flashing, replace the

existing memory module with a replacement module.
Refer to chapter 4 for removing and installing memory

modules.

Processor

Firmware Installed

Incorrectly

If upgrading the processor to a different firmware level,

verify that the firmware chip orientation matches the

upgrade kit directions.

Refer to the following key to determine the status

of the LED indicators:

Indicates the LED is OFF.
Indicates the LED is ON.

Indicates the LED is FLASHING.

If the LEDs indicate:

POWER

PC RUN

CPU FAULT
FORCED I/O
BATTERY LOW

If the LEDs indicate:

POWER

PC RUN

CPU FAULT
FORCED I/O
BATTERY LOW