Setting Up the DH-485 Network

A–13

Grounding and Terminating the DH-485 Network

One (only one) of the link couplers at the end of the link must have
Terminals 1 and 2 of the network connector jumpered together. This
provides an earth ground connection for the shield of the communication
cable.

Link couplers at both ends of the network must have Terminals 5 and 6 of the
link connectors jumpered together. This connects the termination impedance
(of 120

) that is built into each link coupler as required by the DH–485

specification. See the figure below for the proper jumpering.

End-of-Line Termination

Belden #9842 Cable

(1219 m) 4000 ft Maximum

Jumper

Jumper

Jumper

1

2

3

4

5

6

1

2

3

4

5

6