Chapter 8
Troubleshooting

8–7

The Following

Error Exists

Probable Cause

Recommended Action

System does

not operate per

programmed

forces.

User Programmed

Forces are Not

Enabled

1. Monitor program file online and identify programmed

forces.

2. Enable appropriate forces and test system conditions

again. Once forces are enabled, the FORCED I/O LED

goes on steady.

Refer to either the Hand-Held Terminal User Manual,

Catalog Number 1747-NP002, or the Advanced

Programming Software User Manual, Catalog Number

1747-NM002.

The Following

Error Exists

Probable Cause

Recommended Action

CPU Major

Error with Low

or No Battery

Back-up

Loss of RAM

during Power

Down Period

1. Verify battery is connected. See page

7-4

.

2. Replace the battery. See page 7-4.
3. Refer to processor major fault recommended action

steps.

Refer to either the Hand-Held Terminal User Manual,

Catalog Number 1747-NP002, or the Advanced

Programming Software User Manual, Catalog Number

1747-NM002.

Refer to the following key to determine the status

of the LED indicators:

Indicates the LED is OFF.
Indicates the LED is ON.

Indicates the LED is FLASHING.

Regardless of any other LED status indicator condiĆ

tions, always replace the battery when the BATTERY

LOW LED is on if you want RAM battery backup. If

you want to back up RAM with a capacitor, add or

replace the BATTERY LOW LED jumper.

If the LEDs indicate:

POWER

PC RUN

CPU FAULT
FORCED I/O
BATTERY LOW

If the LEDs indicate:

POWER

PC RUN

CPU FAULT
FORCED I/O
BATTERY LOW