Appendix A
Setting Up the DH-485 Network

A–12

The table below shows wire/terminal connections for DH–485 connectors for
old Belden #9842.

For this Wire/Pair

Connect this Wire

To this Terminal

Shield/Drain

Non-jacketed

Terminal 2 - Shield

Black/White

Black

Cut back - no connection

Black/White

White

Terminal 3 - (Common)

Black/Red

Black

Terminal 4 - (Data B)

Black/Red

Red

Terminal 5 - (Data A)

To prevent confusion when installing the communication cable, cut back the black wire immediately after the

the insulation jacket is removed. This wire is not used by DH-485.

The table below shows wire/terminal connections for DH–485 connectors for
new Belden #9842.

For this Wire/Pair

Connect this Wire

To this Terminal

Shield/Drain

Non-jacketed

Terminal 2 - Shield

Blue/White

White with Blue Stripe

Cut back - no connection

Blue/White

Blue with White Stripe

Terminal 3 - (Common)

White/Orange

White with Orange Stripe

Terminal 4 - (Data B)

White/Orange

Orange with White Stripe

Terminal 5 - (Data A)

To prevent confusion when installing the communication cable, cut back the white with blue stripe wire

immediately after the the insulation jacket is removed. This wire is not used by DH-485.

Important: In Series A 1747–AIC, terminal 5 was called DATA B and

terminal 4 was called DATA A. In this case, use terminal
numbers only and ignore signal names DATA B and DATA A.
The internal circuitry of the Series A is the same as Series B.