Chapter 8
Troubleshooting

8–6

The Following

Error Exists

Probable Cause

Recommended Action

Initial CPU Factory

Power-up

Condition

1. Refer to chapter 6 and follow the start-up procedures.
2. Clear processor memory to get rid of the flashing CPU

FAULT LED.

CPU Major

Fault

Hardware/Software

Major Fault

Detected

Erratic repetitive

power cycling can

cause a processor

major hardware

fault.

1. Monitor Status File Word S:6 for major error code.
2. Refer to either the Hand-Held Terminal User Manual,

Catalog Number 1747-NP002, or the Advanced

Programming Software User Manual, Catalog Number

1747-NM002, for error codes and additional

troubleshooting information.

3. Remove hardware/software condition causing fault.
4. Clear Status File S:1/13 major error bit, if set.
5. Clear Status File S:5 minor error bits, if set.
6. Clear Status File S:6 major error code (optional).
7. Attempt a processor Run mode entry.
If unsuccessful, repeat recommended action steps above.

The Following

Error Exists

Probable Cause

Recommended Action

System does

not operate per

ladder logic.

User Forced I/O

Disabling

Operation

1. Monitor program file online and identify forced I/O.
2. Disable appropriate forces and test system conditions

again.

Refer to either the Hand-Held Terminal User Manual,

Catalog Number 1747-NP002, or the Advanced

Programming Software User Manual, Catalog Number

1747-NM002.

Refer to the following key to determine the status

of the LED indicators:

Indicates the LED is OFF.
Indicates the LED is ON.

Indicates the LED is FLASHING.

If the LEDs indicate:

POWER

PC RUN

CPU FAULT
FORCED I/O
BATTERY LOW

If the LEDs indicate:

POWER

PC RUN

CPU FAULT
FORCED I/O
BATTERY LOW