Chapter 1
Selecting Your Hardware Components

1–19

Example

Increasing the load current by 100mA decreases the transient time from
approximately 7 ms to less than 2.5 ms. To calculate the size of the resistor
added in parallel to increase the current, use the following information:

R (Ohms)

V (Volts)
I (Amps)

Resistor value (Ohms) = Applied voltage (Volts) / Desired current (Amps)

= 24 / 0.1

P (Watts) = I

2

(Amps) x R (Ohms)

Actual Power (Watts) = (Desired Current)

2

x Resistor Value

Resistor size = 2 x Actual power (Watts)

= 2 x 2.4

Round resistor size to 5 Watts.

= 2.4 (Watts)

=

24V = your applied voltage
Need 100mA of load current to reduce the transient to < 2.5 ms. (taken from graph on

previous page)

= 240 (Ohms)

= (0.1)

2

x 240

= 4.8 (Watts)

You need a resistor rated for 240 Ohms at 5 Watts to increase the load current
by 100mA; thus decreasing the transient time from approximately 7 ms to
less than 2.5 ms.