High-speed counter input compatibility – Rockwell Automation 1747-L40 SLC 500 Fixed Hardware Style User Manual

Page 61

Advertising
background image

Chapter 4
Installing Your Hardware Components

4–6

beneath the battery connector OR to the right of the battery connector.

J2

J2

The High-Speed Counter jumper is located either

4. Replace the cover.

High-Speed Counter Input Compatibility

The high–speed counter input circuit has the following characteristics:

nominal input impedance of

1200

on–state voltage of 10–30 VDC

nominal input current draw of 20mA

minimum pulse width of 62.5

µ

sec.

Your input device or encoder must be single–ended and be compatible with
the specifications of the high–speed counter input. See the table below for
more information.

For an Input Device or Encoder that Is

Use an HSC Input Circuit that Is

Sourcing

Sinking

Open Collector/ Sinking

Sourcing

Open Collector with Pull-up Resistor

Sinking

Advertising