Emergency-stop switches – Rockwell Automation 1747-L40 SLC 500 Fixed Hardware Style User Manual

Page 45

Advertising
background image

Chapter 2
System Installation Recommendations

2–6

Emergency-Stop Switches

Adhere to the following points concerning emergency–stop switches:

Do not program emergency–stop switches in the controller program. Any
emergency–stop switch should turn off all machine power by turning off
the master control relay.

Observe all applicable local codes concerning the placement and labeling
of emergency–stop switches.

Install emergency–stop switches and the master control relay in your
system. Make certain that relay contacts have a sufficient rating for your
application. Emergency–stop switches must be easy to reach.

The figure below shows the Master Control Relay Wired in Grounded
System.

Disconnect

L1

L2

Isolation

Transformer

Fuse

Operation of either of these contacts will remove

power from the controller external I/O circuits,

stopping machine motion.

MCR

MCR

MCR

Emergency-Stop

Push Button

Overtravel

Limit Switch

Stop

Start

Suppr.

230 VAC

MCR

(Lo)

(Hi)

Incoming Line Terminals. Connect to

115 VAC terminals of Power Supply.

DC Power Supply.

Use N.E.C. Class 2

for UL Listing.

MCR

+

Ċ

115 VAC

X1

X2

Incoming line terminals. Connect to

24 VDC terminals of Power Supply.

24 VDC

I/O Circuits

115 VAC

I/O Circuits

230 VAC

I/O Circuits

Master Control Relay (MCR)

Cat. No. 700-PK400A1

Fuse

Fuse

Suppressor

Cat. No. 700-N24