Output Specifications

The following table details the output specifications for SLC 500 Fixed I/O
Units.

Outputs

Specifications

Output Voltage

85-265 VAC

Continuous Current (per output)

0.5 Amp at +30

°

C

0.25 Amp at +60

°

C (maximum)

Minimum Load Current

10mA

Triac

Turn-On Time

0.1 milliseconds (maximum)

Triac

Turn-Off Time

10 milliseconds (maximum)

Maximum Off-State Leakage Current

2mA

Maximum On-State Voltage Drop

1.5V @ 0.5 Amps

Maximum Surge Current

10 Amps for 25 milliseconds

Output Voltage

10-50 VDC

Continuous Current (per output)

0.5 Amp at +30

°

C

0.25 Amp at +60

°

C (maximum)

Minimum Load Current

1mA

Transistor Sink &

Source

Turn-On Time

0.1 millisecond (maximum)

Source

Turn-Off Time

1 millisecond (maximum)

Maximum Off-State Leakage Current

1mA

Maximum On-State Voltage Drop

1.5V @ 0.5 Amps

Maximum Surge Current

3.0 Amps for 25 milliseconds

Output Voltage Range

5-265 VAC, 5-125 VDC

Continuous Current (per output)

2.5 Amps (maximum)

Continuous Current (per group)

8 Amps (maximum)

Relay

Maximum Load (per chassis)

1440 VA

Relay

Turn-On Time

10 milliseconds (maximum)

Turn-Off Time

10 milliseconds (maximum)

Maximum Off-State Leakage Current

0mA

Minimum Load Current at 5 VDC

10mA

Repeatability is once every 1 second at +30

°

C. Repeatability is once every 2 seconds at +60

°

C.

Refer to the wiring diagrams for output groupings on the fixed I/O chassis.

Surge suppression across the output device is recommended to protect relay contacts.

Advertising