Appendix C
RS-232 Communication Interface

C–12

PLC–5 (Channel 0) to a Modem (Hardware Handshaking Enabled)

DCD

1

2

3

4

5

6

7

8

8

3

2

20

7

6

4

5

RXD

TXD

DTR

COM

DSR

RTS

CTS

GND

1

8

2

20

7

6

4

5

22

3

DCD

NC

RXD

TXD

DTR

COM

DSR

RTS

CTS

25 Pin PLC–5 (ch. 0)

9 Pin

25 Pin

(DTE)

(DCE)

Modem

9

22

RI

Connect to the shield of the cable.

PLC–5 (Channel 0) to a 5/03 Processor, IBM AT, 1770–KF3, 1773–KA,
5130–RM, PLC–5, 1747–KE, or 1746–BAS (Hardware Handshaking
Disabled)

DCD

1

3

2

4

5

6

7

8

8

2

3

20

7

6

4

5

TXD

RXD

DTR

COM

DSR

RTS

CTS

GND

1

8

2

20

7

6

4

5

22

3

DCD

NC

RXD

TXD

DTR

COM

DSR

RTS

CTS

9 Pin

25 Pin

(DTE)

(DTE)

Peripheral

25 Pin PLC–5 (ch. 0)

Device

You can also use cable 1747-CP3.

Jumpers are only needed if you cannot disable the hardware handshaking on the port.

Connect to the shield of the cable.