Page 66

Advertising
background image

Chapter 5
Wiring Your Control System

5–3

Sinking Device with Sourcing Input Module Circuit

The field device is on the negative side of the power supply between the
supply and the input terminal. When the field device is activated, it sinks
current from the input circuit.

DC POWER

SUPPLY

+

_

Input

VDC

DC

INPUT

CIRCUIT

I

FIELD DEVICE

Sinking Device with Sourcing Output Module Circuit

The field device is on the negative side of the power supply between the
supply and the output terminal. When the output is activated, it sources
current to the field device.

DC POWER

SUPPLY

+

_

VDC

DC Com

DC

OUTPUT

CIRCUIT

I

Out

FIELD DEVICE

Sourcing Device with Sinking Output Module Circuit

The field device is on the positive side of the power supply between the
supply and the output terminal. When the output is activated, it sinks current
from the field device.

DC POWER

SUPPLY

+

_

VDC

DC Com

DC

OUTPUT

CIRCUIT

I

Out

FIELD DEVICE

Advertising