Module addressing, Appendix e, Appendix – Rockwell Automation 1769-IT6 Compact I/O 1769-IT6 Thermocouple/mV Input Module User Manual

Page 139

Advertising
background image

Rockwell Automation Publication 1769-UM004B-EN-P - March 2010

139

Appendix

E

Module Configuration by Using a
MicroLogix 1500 System and RSLogix 500
Software

This appendix examines the 1769-IT6 module’s addressing scheme and describes
module configuration by using RSLogix 500 and a MicroLogix 1500 controller.

Module Addressing

This memory map shows the input and configuration image tables for the
module. For detailed information on the image table, see

Chapter 4

.

Figure 55 - Memory Map for Input and Configuration Image Tables

Channel 0 Data Word

Word 0
Word 1
Word 2
Word 3

Word 4

Word 5

Channel 1 Data Word
Channel 2 Data Word
Channel 3 Data Word

General/Open-Circuit Status Bits

Over-/Under-range Bits

Channel 0 Configuration Word
Channel 1 Configuration Word
Channel 2 Configuration Word
Channel 3 Configuration Word

I:e.0
I:e.1

I:e.2

I:e.3
I:e.4
I:e.5

Word 0
Word 1
Word 2
Word 3

Address

Input Image

8 words

Configuration

File

7 words

Slot e

Slot e

Input Image

File

Configuration

File

Memory Map

Bit 15

Bit 0

Channel 4 Data Word
Channel 5 Data Word

Word6

Word 7

I:e.6
I:e.7

Channel 4 Configuration Word
Channel 5 Configuration Word

Word 4
Word 5

Enable/Disable Cyclic Calibration

Word 6

Refer to
your
controller
manual for
the
addresses.