18

Rockwell Automation Publication 1769-UM004B-EN-P - March 2010

Chapter 2 Quick Start for Experienced Users

The module’s maximum current draw is:

• 100 mA for 5V DC.
• 40 mA for 24V DC.

1.

Check that the bus lever of the module to be installed is in the unlocked
(fully right) position.

2.

Use the upper and lower tongue-and-groove slots (1) to secure the
modules together (or to a controller).

3.

Move the module back along the tongue-and-groove slots until the bus
connectors (2) line up with each other.

4.

Push the bus lever back slightly to clear the positioning tab (3) by using
your fingers or a small screwdriver.

5.

Move the bus lever fully to the left (4) until it clicks to allow
communication between the controller and module.

Step 1

Be sure that your 1769 system power supply

(1)

has sufficient current

output to support your system configuration.

Reference

Chapter 3

(Installation and Wiring)

(1) The system power supply could be catalog number 1769-PA2, 1769-PB2, 1769-PA4, 1769-PB4, or the internal supply of the

MicroLogix 1500 packaged controller.

Step 2

Attach and lock the module.

Reference

Chapter 3

(Installation and Wiring)

TIP

The module can be panel or DIN rail mounted. Modules can be
assembled before or after mounting.

ATTENTION: Remove power before removing or inserting this module. If
you remove or insert a module with power applied, an electrical arc may
occur.

IMPORTANT

To reduce the effects of electrical noise, install the 1769-IT6 module at
least two slots away from Compact I/O 120/240V AC power supplies.