Chapter 4 Module Data, Status, and Channel Configuration

Channel Cut-off Frequency

The filter cut-off frequency, -3 dB, is the point on the frequency response curve
where frequency components of the input signal are passed with 3 dB of
attenuation. This table shows cut-off frequencies for the supported filters.

All input frequency components at or below the cut-off frequency are passed by
the digital filter with less than 3 dB of attenuation. All frequency components
above the cut-off frequency are increasingly attenuated as shown in the graphs on

page 49

.

Table 5 - Filter Frequency versus Channel Cut-off Frequency

Filter Frequency

Cut-off Frequency

10 Hz

2.62 Hz

50 Hz

13.1 Hz

60 Hz

15.7 Hz

250 Hz

65.5 Hz

500 Hz

131 Hz

1 kHz

262 Hz