Configuring Your 1769-IT6 Module with the Generic Profile for CompactLogix Controllers in RSLogix 5000 Software Appendix F

Click OK and this default Generic Profile dialog box appears.

First, choose the Comm Format (‘Input Data – INT’ for the 1769-IT6 module),
then fill in the name field. For this example, ‘IT6’ is used to help identify the
module type in the Controller Organizer. The Description field is optional and
may be used to provide more details concerning this I/O module in your
application.

The slot number must be selected next, although it will begin with the first
available slot number, 1, and increments automatically for each subsequent
Generic Profile you configure. For this example, the 1769-IT6 thermocouple
module is located in slot 1.

Enter the Assembly Instance numbers and their associated sizes for the 1769-IT6
module into the Generic Profile.

Table 17 - 1769-IT6 Comm Format, Assembly Instance, and Size Values

1769 I/O
Module

Comm Format Parameter

Assembly
Instance

Size (16-bit)

IT6

Input Data –
INT

Input
Output
Config

101
104
102

8
0
8