Specifications

Table 12 - General Specifications - 1769-IT6

Attribute

1769-IT6

Dimensions (HxDxW), approx.

118 x 87 x 35 mm (4.65 x 3.43 x 1.38 in.)
height including mounting tabs is 138 mm (5.43 in.)

Shipping weight (with carton), approx.

276 g (0.61 lb)

Storage temperature

-40…85 °C (-40…185 °F)

Operating temperature

0…60 °C (32…140 °F)

Operating humidity

5…95% noncondensing

Operating altitude

2000 m (6561 ft)

Vibration, operating

10…500 Hz, 5 g, 0.030 in. peak-to-peak

Vibration, relay operation

2 g

Shock, operating

30 g, 11 ms panel mounted
(20 g, 11 ms DIN rail mounted)

Shock, relay operation

7.5 g panel mounted (5 g DIN rail mounted)

Shock, nonoperating

40 g panel mounted (30 g DIN rail mounted)

System power-supply distance rating

8 (The module may not be more than 7 modules away
from a system power supply.)

Recommended cable

Belden 8761 (shielded) for millivolt inputs
Shielded thermocouple extension wire for the specific
type of thermocouple you are using. Follow
thermocouple manufacturer’s recommendations.

Agency certification

C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives

Hazardous environment class

Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)

Radiated and conducted emissions

EN50081-2 Class A