Module operation – Rockwell Automation 1769-IT6 Compact I/O 1769-IT6 Thermocouple/mV Input Module User Manual

Page 15

Advertising
background image

Rockwell Automation Publication 1769-UM004B-EN-P - March 2010

15

Overview Chapter 1

Module Operation

When the module receives a differential input from an analog device, the
module’s circuitry multiplexes the input into an A/D converter. The converter
reads the signal and converts it as required for the type of input. The module also
continuously samples the CJC sensors and compensates for temperature changes
at the terminal block cold junction, between the thermocouple wire and the
input channel.

Each channel can receive input signals from a thermocouple or millivolt analog
input device, depending upon how you configured the channel.

When configured for thermocouple input types, the module converts the analog
input voltages into cold-junction compensated and linearized digital temperature
readings. The module uses the National Institute of Standards and Technology
(NIST) ITS-90 standard for linearization for all thermocouple types ( J, K, T, E,
R, S, B, N, C).

When configured for millivolt inputs, the module converts the analog values
directly into digital counts.

18-pin Terminal Block

16-pin Backplane
Connector

1769 Bus

ASIC

Opto--

couplers

(3)

A/D

Converter

Differential

8:1

Multiplexer

Circuits

Input

Protection

Circuitry

Microprocessor

6 Differential

Thermocouple/mV

Inputs

CJC Sensors

+24V DC

24V GND

Isolated Power

Supply

+5V

+15V

GND

-15V

Module

Data

Module

Status

Module

Configuration

Data

Controller