Installation and Wiring Chapter 3
Figure 3 - Wiring Diagram
NC
IN 0+
IN 0-
IN 3+
IN 1 +
IN 3-
IN 1-
IN 4+
IN 2+
IN 4-
IN 2-
IN 5+
IN 5-
NC
+
-
+
-
+
-
CJC 0+
CJC 0-
CJC 1-
CJC 1+
Within 10V DC
Grounded Thermocouple
Grounded Thermocouple
Ungrounded Thermocouple
CJC Sensor
CJC Sensor
TIP
When using an ungrounded thermocouple, the shield must be connected
to ground at the module end.
IMPORTANT
When using grounded and/or exposed thermocouples that are touching
electrically conductive material, the ground potential between any two
channels cannot exceed ±10V DC, or temperature readings will be
inaccurate.