Installation and Wiring Chapter 3

Figure 3 - Wiring Diagram

NC

IN 0+

IN 0-

IN 3+

IN 1 +

IN 3-

IN 1-

IN 4+

IN 2+

IN 4-

IN 2-

IN 5+

IN 5-

NC

+

-

+

-

+

-

CJC 0+

CJC 0-

CJC 1-

CJC 1+

Within 10V DC

Grounded Thermocouple

Grounded Thermocouple

Ungrounded Thermocouple

CJC Sensor

CJC Sensor

TIP

When using an ungrounded thermocouple, the shield must be connected
to ground at the module end.

IMPORTANT

When using grounded and/or exposed thermocouples that are touching
electrically conductive material, the ground potential between any two
channels cannot exceed ±10V DC, or temperature readings will be
inaccurate.