Rockwell Automation 1769-IT6 Compact I/O 1769-IT6 Thermocouple/mV Input Module User Manual

Page 85

Advertising
background image

Rockwell Automation Publication 1769-UM004B-EN-P - March 2010

85

Specifications Appendix A

Module OK status indicator

On: module has power, has passed internal diagnostics,
and is communicating over the bus.
Off: Any of the above is not true.

Channel diagnostics

Over- or under-range and open-circuit by bit reporting

Vendor I.D. code

1

Product type code

10

Product code

36

(1)

Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including
the input signal and the value that floats above ground potential (for example, 30V DC input signal and 20V DC
potential above ground).

(2)

For proper operation, both the plus and minus input terminals must be within ±10V DC of analog common.

(3)

Open-circuit detection time is equal to the module scan time, which is based on the number of enabled
channels, and the filter frequency of each channel.

(4)

Maximum current input is limited due to input impedance.

Table 14 - Repeatability at 25 °C (77 °F)

(1)

(2)

(1)

Repeatability is the ability of the input module to register the same reading in successive
measurements for the same input signal.

(2)

Repeatability at any other temperature in the 0…60 °C (32…140 °F) range is the same as long as the
temperature is stable.

Input Type

Repeatability for 10 Hz
Filter

Thermocouple J

±0.1 °C (±0.18 °F)

Thermocouple N (-110…1300 °C (-166…2372 °F))

±0.1 °C (±0.18 °F)

Thermocouple N (-210…-110 °C (-346…-166 °F))

±0.25 °C (±0.45 °F)

Thermocouple T (-170…400 °C (-274…752 °F))

±0 .1 °C (±0.18 °F)

Thermocouple T (-270…-170 °C (-454…-274 °F))

±1.5 °C (±2.7 °F)

Thermocouple K (-270…1370 °C (-454…2498 °F))

±0.1 °C (±0.18 °F)

Thermocouple (-270…-170 °C (-454…-274 °F))

±2.0 °C (±3.6 °F)

Thermocouple E (-220…1000 °C (-364…1832 °F))

±0.1 °C (±0.18 °F)

Thermocouple E (-270…-220 °C (-454…-364 °F))

±1.0 °C (±1.8 °F)

Thermocouples S and R

±0.4 °C (±0.72 °F)

Thermocouple C

±0.7 °C (±1.26 °F)

Thermocouple B

±0.2 °C (±0.36 °F)

±50 mV

±6 µV

±100 mV

±6 µV

Table 13 - Input Specifications - 1769-IT6

Attribute

1769-IT6

Advertising