Error codes – Rockwell Automation 1769-IT6 Compact I/O 1769-IT6 Thermocouple/mV Input Module User Manual

Page 80

Advertising
background image

80

Rockwell Automation Publication 1769-UM004B-EN-P - March 2010

Chapter 5 Diagnostics and Troubleshooting

Error Codes

This table explains the extended error code.

Table 11 - Extended Error Codes

Error Type

Hex
Equivalent

(1)

Module
Error Code

Extended Error
Information
Code

Error Description

Binary

Binary

No error

X000

000

0 0000 0000

No error

General common
hardware error

X200

001

0 0000 0000

General hardware error; no additional information

X201

001

0 0000 0001

Power-up reset state

Hardware-specific
error

X300

001

1 0000 0000

General hardware error; no additional information

X301

001

1 0000 0001

Microprocessor hardware error; hardware ROM error

X302

001

1 0000 0010

Hardware EEPROM error

X303

001

1 0000 0011

Channel 0 calibration error

X304

001

1 0000 0100

Channel 1 calibration error

X305

001

1 0000 0101

Channel 2 calibration error

X306

001

1 0000 0110

Channel 3 calibration error

X307

001

1 0000 0111

Channel 4 calibration error

X308

001

1 0000 1000

Channel 5 calibration error

X309

001

1 0000 1001

CJC0 calibration error

X30A

001

1 0000 1010

CJC1 calibration error

X30B

001

1 0000 1011

Channel 0 analog/digital converter error

X30C

001

1 0000 1100

Channel 1 analog/digital converter error

X30D

001

1 0000 1101

Channel 2 analog/digital converter error

X30E

001

1 0000 1110

Channel 3 analog/digital converter error

X30F

001

1 0000 1111

Channel 4 analog/digital converter error

X310

001

1 0001 0000

Channel 5 analog/digital converter error

X311

001

1 0001 0001

CJC0 analog/digital converter error

X312

001

1 0001 0010

CJC1 analog/digital converter error

Advertising