Rockwell Automation Publication 1769-UM004B-EN-P - March 2010

Appendix E Module Configuration by Using a MicroLogix 1500 System and RSLogix 500 Software

For example, to obtain the general status of channel 2 of the module located in
slot e, use address I:e.6/2.

Figure 56 - General Status of Channel 2

1769-IT6 Configuration File

The configuration file contains information you use to define the way a specific
channel functions. The configuration file is explained in more detail in

Configuring Channels on page 40

.

The configuration file is modified by using the programming software
configuration screen. For an example of module configuration by using RSLogix
500 software, see

Configuring the 1769-IT6 Module in a MicroLogix 1500

System on page 141

.

TIP

The end cap does not use a slot address.

Table 16 - Software Configuration Ch

annel De

faults

(1)

(1)

May be overridden by the software.

Parameter

Default Setting

Disable/Enable Channel

Disable

Filter Frequency

60 Hz

Input Type

Thermocouple Type J

Data Format

Raw/Proportional

Temperature Units

°C

Open-circuit Response

Upscale

Disable Cyclic Calibration

Enable

I:e.6/2

Input File Type

Slot

Word

Bit

Bit Delimiter

Word Delimiter

Element Delimiter

0

1

2

3

Ada

pter

Compact I/O

Compact I/O

Compact I/

O

En

d Cap

Slot Number