Publication 1734-UM006B-EN-P - August 2005

About the Modules 1-9

Operating Mode Features

The following table summarizes which features are active in each
mode:

Operating Mode Features

The Z Gate/Reset Terminall will operate in one of four modes when
the Store Count feature is in use. The following figures detail the
operation in each mode:

• Store/Continue
• Store/Wait/Resume
• Store-Reset/Wait/Start
• Store-Reset/Start

Store Count Mode 1: Store/Continue

In mode 1, the rising edge of a pulse input on the Z Gate/Reset
terminal causes the current counter value to be read and stored in the
Read Data file. The counter continues counting. The stored count is
available in the Stored/Accumulated Count word. The stored count
information remains until it is overwritten with new data.

Store/Continue

Store Count Mode 2: Store/Wait/Resume

In mode 2, the rising edge of a pulse input on the Z Gate/Reset
terminal reads and stores the current counter value in the
Stored/Accumulated Count word and inhibits counting while the Z

Operating Feature

Counter
Up / Down

Encoder
X1, X2 & X4

Period
/Rate

Rate
Measurement

Preset

Y

Y

N

N

Rollover

Y

Y

N

N

Software Reset

Y

Y

Y

Y

Store Count - Z Gate / Reset 4 modes

Y

Y

N

N

Scale Input Count at Z Gate / Reset

N

N

Y

N

Z Gate / Reset Invert Bit

Y

Y

Y

N

Sample Period

N

N

N

Y

Read, Store Count,
and Continue Counting