Configuration data – Rockwell Automation 1734-IK Encoder/Counter Modules User Manual User Manual

Page 36

Advertising
background image

Publication 1734-UM006B-EN-P - August 2005

3-4 Input and Output Data

Zero frequency Detected (ZD) - This bit is operational when
frequency configurations are programmed (configurations: period/rate
[5], rate measurement [7])
.

In period/rate [5] configuration, counts are acquired during
the ON state of the Z input. At very low frequencies the counter
saturates, indicating a zero frequency detect. The time it takes to
determine a zero frequency in these two configurations can be
as long as 6.7 seconds ( 16,777,216 counts x 1/5MHz x 2 half
cycles of Z ).

In rate measurement [7] configuration pulses on the A input
are counted over a sample interval specified by the time base.
The time it takes to determine a zero frequency in this
configuration will be determined by the sample interval, for
example, time base = 0.300 second (300 milliseconds) to
determine ZF.

Configuration Data

The following represents the configuration data used by the module.

Parameter

Configuration Information

Size (bytes)

1

Set/Get

Counter Configuration

1

2

Set/Get

Filter Selection

1

3

Set/Get

Decimal Position

1

4

Set/Get

Reserved

1

5

Set/Get

Time Base

2

6

Set/Get

Gate Interval

1

7

Set/Get

Scalar

1

8

Set/Get

Rollover Value

4

9

Set/Get

Preset Value

4

10

Set/Get

Counter Control SS Value

1