Publication 1734-UM006B-EN-P - August 2005

3-8 Input and Output Data

Safe State Values (Configuration Word 10)

When either the host transitions to PROGRAM mode or a
communication fault (broken network cable) occurs, the module
copies the safe state word (counter control value) into its real-time
working buffer. The definitions are identical to those described under
Real-time Output Data.

Communicate Real
Time/Nonreal Time
Information

The Encoder/Counter Module uses several words to communicate real
time input and output data as well as non-real time module
information (such as description and revision) and configuration.

Assembly 101 is produced for a polled connection. Assembly 102 is
produced for a Change Of State (COS) connection. Assemblies 103,
104, and 106 are by Explicit message only. Assembly 105 is consumed
in a polled connection.

Data may be read (get) or written (set) using an Explicit Message. For
example, to read the Present Channel Data, assembly 101

10

(65

16

) can

be requested. The following table shows the words which can be
exchanged.

Instances

Services

Field

Bytes

#101 (0x65)

Get

Present Channel Data

4

Status

2

#102 (0x66)

Get

Stored Channel Data

4

Status

2

#103 (0x67)

Get

Present Channel Data

4

Stored Channel Data

4

Status

2

#104 (0x68)

Get

Programming Error Code

2

#105 (0x69)

Set/Get

Counter Control

1

#106 (0x6a)

Set/Get

Counter Configuration

1

Filter Selection

1

Decimal Position

1

Reserved

1

Time Base

2

Gate Interval

1

Scalar

1

Rollover Value

4

Preset Value

4

Counter Control SSV

1