Publication 1734-UM006B-EN-P - August 2005

Access Instantiated Instances 5-3

Assemblies

Available assemblies are:

• Assembly 101 is produced for a polled connection.
• Assembly 102 is produced for a Change Of State (COS)

connection.

• Assemblies 103, 104 and 106 are by Explicit message only.
• Assembly 105 is consumed in a polled connection .

Data may be read (get) or written (set) using an Explicit Message. For
example, to read the Present Channel Data, assembly 101

10

(65

16

) can

be requested.

Data is ordered as followed (byte 0 is the least significant byte):

8 bit byte

Byte 0

16 bit word

Byte 0, byte 1

32 bit long word

Byte 0, byte 1, byte 2, byte 3

In this example, assembly 101,

Service

Class

Instance

Attribute

0E (Get)

04 (Assembly)

65 (Present Data)

03 (Data Attribute)

Instances

Services

Field

Bytes

#101 (0x65)

Get

Present Channel Data

4

Status

2

#102 (0x66)

Get

Stored Channel Data

4

Status

2

#103 (0x67)

Get

Present Channel Data

4

Stored Channel Data

4

Status

2

#104 (0x68)

Get

Programming Error Code

2

#105 (0x69)

Set/Get

Counter Control

1