Counter configuration (configuration word 1), Filter selection (configuration word 2, Filter selection – Rockwell Automation 1734-IK Encoder/Counter Modules User Manual User Manual

Page 37: This byte sets the a/b/z input filters

Advertising
background image

Publication 1734-UM006B-EN-P - August 2005

Input and Output Data 3-5

Counter Configuration (Configuration Word 1)

Use this byte to select the type of counter desired.

Filter Selection (Configuration Word 2

This byte sets the A/B/Z input filters

Filter Selection

07

06

05

04

03

02

01

00

ZI

MD

CF

Counter 0

0

0

0

0

Counter

0

0

0

1

Encoder X1

0

0

1

0

Encoder X2

0

0

1

1

Reserved

0

1

0

0

Encoder X4

0

1

0

1

Period/Rate

0

1

1

0

Reserved

0

1

1

1

Rate Measurement

0

0

0

Store Count Disabled

0

0

1

Mode 1 - store/continue

0

1

0

Mode 2 - store/wait/resume

0

1

1

Mode 3 - store, reset/wait/start

1

0

0

Mode 4 - store, reset/start

1

0

1

Reserved

1

1

0

Reserved

1

1

1

Reserved

0

Z input - 0 = not inverted

1

Z input - 1 = inverted

07

06

05

04

03

02

01

00

0

ZF

BF

AF

FS

0

0

0

0

No Filter

0

0

0

1

50kHz (10

µs + 0µs/-1.6µs)

0

0

1

0

5kHz (100

µs + 0µs/-13.2µs)

0

1

0

0

500Hz (1.0ms + 0

µs/-125µs)

1

0

0

0

50Hz (10ms + 0ms/-1.25ms)

0

A input not filtered

1

A input filtered

0

B input not filtered

1

B input filtered

0

Z input not filtered

1

Z input filtered