Publication 1734-UM006B-EN-P - August 2005

6-2 Troubleshoot the Module

Indication

Probable Cause

Network Status

Off

Device is not online.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator.

Flashing Green

Device is online, but has no connections in the established
state.

Green

Device online and has connections in the established state.

Flashing Red

One or more I/O connections are in timed-out state

Red

Critical link failure with failed communication device is
present. Device detected error that prevents it
communicating on the network.

Flashing
Red/Green

Communication faulted device - the device detected a
network access error and is in communication faulted state.
Device received and accepted an Identify Communication
Faulted Request with long protocol message.

Indication

Probable Cause

Input Status

Off

Input is inactive.

Yellow

Input is active and under control.