Store-reset/start – Rockwell Automation 1734-IK Encoder/Counter Modules User Manual User Manual

Page 20

Advertising
background image

Publication 1734-UM006B-EN-P - August 2005

1-10 About the Modules

Gate/Reset terminal is high. Counting resumes on the falling edge of
the pulse at the Z Gate/Reset terminal. The stored count information
remains until it is overwritten with new data.

Store/Wait/Resume

Store Count Mode 3: Store-Reset/Wait/Start

In mode 3, the rising edge of a pulse input on the Z Gate/Reset
terminal stops counting, reads, and stores the current counter value in
the Stored/Accumulated Count word, and resets the counter to zero.
The counter does not count while the input pulse on the Z Gate/Reset
terminal is high. Counting resumes from zero on the falling edge of
the pulse at the Gate/Reset terminal. The stored count information
will remain until it is overwritten with new data.

Store-Reset/Wait/Start

Store Count Mode 4: Store-Reset/Start

In mode 4, the rising edge of a pulse input on the Z Gate/Reset
terminal will store the current counter value in the
Stored/Accumulated Count word and reset the counter to zero. The
counter will continue counting while the Z Gate/Reset terminal is
high. The stored count information will remain until it is overwritten
with new data.

Store-Reset/Start

Store Count

Resume Counting

Stop Counting

and Reset to zero

from zero

Counter has stopped Counting

Start Counting

Stop Count, Store,

and Reset to zero

Start Counting

Continue Counting

Store Count,