Network address switch value 001, Default factory configuration – Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input/Output User Manual

Page 16

Advertising
background image

8

Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012

Chapter 2 Install Your ArmorBlock Module

5.

Replace switch dust caps. Make sure not to over tighten.

6.

Reapply power.

7.

Record IP address on product label found on the side of enclosure.

Set Network Address

When the switches are set to a valid number, the I/O block’s IP address is
192.168.1.xxx, where xxx represents the number set on the switches. The I/O
block’s subnet mask is 255.255.255.0 and default gateway address is set to
192.168.1.1.

When the I/O block uses the network address set on the switches, the I/O block
does not have a host name assigned to it or use any Domain Name Server.

If the switches are set to an invalid number (for example, 000 or a value greater
than 254 excluding 888), the I/O block checks to see if DHCP is enabled. If
DHCP is enabled, the I/O block asks for an address from a DHCP server. The
DHCP server also assigns other Transport Control Protocol (TCP) parameters.
(The modules are shipped with the network switches set to 999.)

If DHCP is not enabled, the I/O block uses the IP address (along with other
TCP configurable parameters) stored in nonvolatile memory.

Network Address Switch value 001

The module IP address cannot be the same as the gateway address. If the address
switches are set to 001, the module IP address becomes 192.168.1.1, which is the
same as the default gateway address. In this case, the module gateway address will
be set to 0.0.0.0.

Default Factory Configuration

The switch value 888 resets the module to default factory configuration on power
up. The module will not operate properly when powered up with this setting.
The switches must be set to a different (and valid) value and then power cycled
after a reset.

While in reset state, the module LED flashes red and the network LED goes off.

0

2

4

6

8

0

2

4

6

8

0

2

4

6

8

Example shows network switches
set at 163, which sets the module
IP address to 192.168.1.163.

44233

Note: You need to remove the
protective switch dust caps before
you can adjust the address
settings.

Advertising
This manual is related to the following products: