Rockwell Automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-Point Analog Input/Output User Manual

Page 26

Advertising
background image

18

Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012

Chapter 3 Configure Your Analog Input and Output Modules with RSLogix 5000 Software

4.

The New Module dialog opens.
Configure the bridge module as illustrated below.

Note that we have entered the following properties in this example:

The local 1756-EN2T communication module will communicate with the
1732E ArmorBlock module on Ethernet. Before you can communicate with your
module, you need to add it as a

child of the 1756-EN2T communication module.

For more information about using 1756 controller and EtherNet/IP products, see
publication

ENET-UM001

.

Add the I/O module as a child of the 1756-EN2T module

1.

Right-click the Ethernet folder that appears below the 1756-EN2T bridge
you added to the I/O Configuration tree and select New Module.

A. Name the bridge.

B. Enter the IP address.

C. Select slot 3 for the EtherNet/IP bridge.

D. Make sure the Minor Revision number

matches your module revision number.

E. Choose an Electronic Keying method.

For more information, see

page 23

.

F. Click OK.

Name

TEST_1756EN2T

IP address

192.168.1.20

Slot

3

Revision

3.1

Electronic Keying

Compatible Module

Advertising
This manual is related to the following products: