Chapter 6 Troubleshoot the Modules

Check for Faults

In addition to the status indicators on the module, RSLogix 5000 software alerts
you to fault and other conditions in one of three ways:

Indicator Status for Modules

Indicator

Status

Description

Module status

Off

No power applied to the device.

Flashing red/
green

The module is performing POST (Power-On Self Test), which
completes within 30 s.

Green

Device operating normally.

Flashing red

Module has experienced a recoverable fault.

Red

Unrecoverable fault – may require device replacement.

Network status

Off

The device is not initialized or the module does not have an IP
address.

Flashing green

The device has no CIP connections. The device has an IP
address, but no CIP connections are established.

Green

Device is online, has an IP address. CIP connections are
established.

Flashing red

One or more connections have timed out.

Red

The module has detected that its IP address is
already in use.

Flashing red/
green

The module is performing a power-on self test (POST).

Network link
status
(Link 1/Link 2)

Off

No link established.

Green

Link established on indicated port at 100 Mbps.

Flashing green

Link activity present on indicated port at 100 Mbps.

Yellow

Link established on indicated port at 10 Mbps.

Flashing yellow

Link activity present on indicated port at 10 Mbps.

Auxiliary
Power status

Off

Auxiliary power off or not connected.

Green

Auxiliary power applied to device.

I/O status

Off

The input or output channel is inactive, can be calibrated.

Flashing Green

Channel is calibrating.

Green

1732E-IF4M12R – Normal operation, inputs being scanned.
1732E-OF4M12R – The output is active and under control.

Flashing Red

1732E-IF4M12R – Fault. Channel is at end of range.
1732E-OF4M12R – Output fault. The output is open (current
mode only), or a low/high clamp alarm is present.

Red

1732E-OF4M12R – Auxiliary power disconnected or off.