Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012

77

Appendix

C

Module Tag Definitions

The 1732E-IF4M12R and 1732E-OF4M12R modules have the following sets
of tags:

• Configuration
• Input
• Output (for 1732E-OF4M12R only)

Module Tags for 1732E-IF4M12R

Input Tags (1732E-IF4M12R)

Tag Name

Data Type

Definition

I.Fault

DINT

Collection of all module level fault bits.

I.Ch0Data
I.Ch1Data
I.Ch2Data
I.Ch3Data

INT

The channel input signal represented in counts where -32,768 counts is the minimum detectable input signal and
32,767 counts is the maximum detectable.

I.Ch0Fault
I.Ch1Fault
I.Ch2Fault
I.Ch3Fault

BOOL

Individual channel fault status bit. Indicates a ‘hard’ fault has occurred on the channel that means: calibration is
ongoing; or if an input, an overrange or underrange condition is present These bits also are set by the controller if
communication is lost with the I/O module.

I.Ch0Calibration
I.Ch1Calibration
I.Ch2Calibration
I.Ch3Calibration

BOOL

Indicates if calibration is currently in progress on a channel.

I.Ch0Lalarm
I.Ch1Lalarm
I.Ch2Lalarm
I.Ch3Lalarm

BOOL

Low alarm bits that set when the input signal moves beneath the configured low alarm trigger point,
C.Ch<0...3>LAlarmLimit. Remains set until the input signal moves above the trigger point, unless latched via
C.Ch<0...3>LimitAlarmLatch.

I.Ch0HAlarm
I.Ch1HAlarm
I.Ch2HAlarm
I.Ch3HAlarm

BOOL

High alarm bit that sets when the input signal moves above the configured high alarm trigger point,
Ch<0…3>HAlarmLimit. emains set until the input signal moves below the trigger point, unless latched via
Ch<0…3>LimitAlarmLatch of the high alarm trigger point.

I.Ch0LLAlarm
I.Ch1LLAlarm
I.Ch2LLAlarm
I.Ch3LLAlarm

BOOL

Low low alarm bit that sets when the input signal moves beneath the configured low low alarm trigger point,
Ch<0…3>LLAlarmLimit. Remains set until the input signal moves above the trigger point, unless latched via
Ch<0…3>LimitAlarmLatch.

I.Ch0HHAlarm
I.Ch0HHAlarm
I.Ch0HHAlarm
I.Ch0HHAlarm

BOOL

High high alarm bit that sets when the input signal moves above the configured high high alarm trigger point,
Ch<0…3>LimitAlarmLatch.

I.Ch0Underrange
I.Ch1Underrange
I.Ch1Underrange
I.Ch1Underrange

BOOL

Alarm bits indicating the channel’s input is less than the minimum detectable input signal.